Surge Arrester 2-Electrode-Arrester

A71-H10XG Ordering code: B88069X3880T502

DC spark-over voltage 1) 2) Impulse spark-over voltage at 100 V/us - for 99 % of measured values - typical values of distribution at 1 kV/us - for 99 % of measured values - typical values of distribution

1000 15 < 1300 < 1200 < 1400 < 1300 10 10 10 65 > 10 <1 ~ 20 ~1 ~ 180 ~ 1.5 -40 ... +90 40/ 90/ 21 1000 YY O
1000 YY O - Nominal voltage - Year of production - Non radioactive

V % V V V V kA kA A A G pF V A V g C

Nominal impulse discharge current (wave 8/20 us) Single impulse discharge current (wave 8/20 us) Nominal alternating discharge current (50 Hz, 1 s) Alternating discharge current (50 Hz, 9 cycles) Insulation resistance at 100 Vdc Capacitance at 1 MHz Arc voltage at 1 A Glow to arc transition current Glow voltage Weight Operation and storage temperature Climatic category (IEC 60068-1) Marking, green

1)

At delivery AQL 0.1 level II and AQL 0.65 level II at 1000 V 10 %; DIN ISO 2859 2) In ionized mode Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845